Lab testing · Test type

Shear Panel & Diaphragm Testing

Customer questionHow stiff and strong is our wall panel — measured as a built diaphragm, not assumed?

The short answer

What this test tells you

A shear panel — or diaphragm — is a wall, floor, or roof assembly asked to resist force acting in its own plane rather than pushing on it face-on. For a wall, that is the wind or earthquake load trying to shove the building sideways. We build your panel the way it is actually built: same panels, same fasteners, same spacing, same seam and edge details. Then we mount it in a cantilever frame, shear it sideways in its own plane, and record how much load it takes and how far it moves along the way — through to the point where something gives, which we photograph and describe. What you get back is a measured record of the panel we tested: how strong, how stiff, and what governed. Your engineer decides what those numbers mean for a project. Testing turns assumptions into evidence.

Engineers: skip to the technical detail

Why it matters

What decision does the result support?

A wall panel that participates in the lateral-force-resisting system carries in-plane shear as an assembled system — panels, structural fasteners, sidelaps, and framing acting together — and the project design basis for that behavior is normally a conservative analytical model. The test does not replace the model. It shows whether the analytical basis appears conservative against measured behavior, records how the assembly behaves across the load range, and documents what governs when it stops behaving that way. Custom and proprietary panel systems rarely fit a clean prescriptive pathway, so the analytical basis carries more weight for them and deserves more evidence behind it. Testing turns assumptions into evidence: validation of the design basis, behavior evidence, and a failure mechanism a reviewer can actually examine.

What the evidence supports

  • engineering review
  • plan check response
  • product development
  • AMM (alternate methods and materials) submissions
  • engineering evaluation reports
  • certification evidence packages

Typical project situations

  • Validating the conservative analytical basis behind a custom or proprietary wall panel system
  • Characterizing in-plane shear behavior of a modular partition or shear-wall panel product
  • Supporting an AMM (alternate methods and materials) submission with measured behavior and failure modes
  • Answering engineering review or plan check questions about an assembled panel’s in-plane stiffness
  • Evaluating how a fastener pattern, sidelap, or edge detail change moves panel behavior
  • Product development on a panel system that no prescriptive pathway describes

What you receive

Test reports

The primary deliverable is the test report: what was tested, to which reference, with what instrumentation, what was measured, and what the result means for the assumption in question. What a test report contains is described on the Test reports page.

Important distinctions

What does this test not prove?

Answer

A single connection or fastener test and a diaphragm test answer different questions: the first measures one interface, the second measures the assembly — panel field, structural fasteners, sidelaps, and framing acting together. The governing mechanism reported here is the first observed major event that interrupts intended load transfer; it is not a chronology of internal initiation, and the evidence supports first-observed governance only. Failure mechanism and stiffness mechanism are also distinct: the connections may govern failure while the panel field still contributes materially to stiffness, so attributing the whole response to one mechanism overstates what was measured. The test validates the analytical design basis; it does not replace it. And AISI S907 measures behavior, while AISI S310 is the design standard under which design values and their safety and resistance factors are derived downstream — a custom or proprietary wall panel does not automatically earn S310 tabulated design values by being tested. Wall diaphragms may also be subject to additional requirements from the applicable building code, particularly for seismic resistance.

The question is not simply whether something held load. The question is whether the assumptions behind the design remain valid — and every test answers only the question it was designed to ask.

Whether this method is inside SMHE Lab’s accredited scope is stated in the Scope of Accreditation. Ask us to confirm before relying on an accredited result.

The assumption

What assumption does this test check?

Assumption this test checks

The assembled panel delivers the in-plane shear stiffness and strength that the lateral analysis assigns to it — as a built diaphragm, with its actual panels, fasteners, and sidelaps, rather than as an idealized membrane.

What it evaluates

What does this test evaluate?

Shear panel and diaphragm testing per AISI S907 loads a framed cold-formed steel panel assembly in its own plane using the cantilever test method. The standard covers floor, roof, and wall diaphragm construction; a wall diaphragm is the vertical case — a shear wall, bearing or non-bearing, designed to resist forces acting in the plane of the wall. The specimen is the assembly rather than a component: steel panels fastened to the support members of a rectangular test frame with structural fasteners, and fastened to each other along their edges with sidelap connections — both spaced as intended for end use. Three quantities are measured — the nominal diaphragm web shear strength [resistance] per unit length, Sn, taken from the maximum applied load once the separately measured bare-frame contribution has been accounted for; the diaphragm web shear stiffness G′, determined at Pd = 0.4Pmax; and the flexibility factor F = 1/G′ — reported together with the load–displacement record and the observed failure mechanism. Behavior in these assemblies is typically connection-governed, so the panel field, the fastener pattern, and the edge and sidelap conditions are what move the result. The measured quantities and failure modes are reported for interpretation by a qualified engineer; they are not themselves design values.

Technical detail

How does the test work?

The specimen is a cantilever diaphragm test assembly: a rectangular test frame on which the cold-formed steel panels are placed and fastened using connections spaced as intended for end use, with load applied along one side of the frame and supports provided at the opposite side. Assembly size is not less than five full-width panels with an aspect ratio between 0.6 and 1.67, unless the intended end use itself falls outside those limits. Framing members supporting the panels are permitted to be steel, concrete, wood, or a combination of materials representative of the intended end use; the standard advises that the failure mechanism and the flexibility of the panel-to-frame connections should be representative of that end use, because they weigh heavily on the result. Before the panels are installed, the bare frame is run through the same load test procedure so its strength and stiffness are known over a deflection range greater than the assembly will reach, and its contribution is then corrected out of the results — a two percent threshold governs whether that correction applies at all. Loading proceeds in approximately equal increments with at least ten sets of load and displacement readings recorded before the maximum load is reached, at a rate slow enough that Pmax is achieved in not less than ten minutes; at approximately one-quarter and one-half of the estimated maximum load, the load is lowered to the initial level and the residual displacement recorded. Static testing in the horizontal orientation is SMHE’s typical arrangement, instrumented with linear transducers, a load cell, hydraulic ram and pump, and an SMHE-developed data acquisition system. Three quantities come out of the load–net-deflection record: the nominal shear strength [resistance] per unit length, Sn = Pn / b; the shear stiffness of the diaphragm web, G′ = (Pd × a) / (δd × b), evaluated at Pd = 0.4Pmax; and the flexibility factor, F = 1/G′. A minimum of three tests applies per Section K2.1.1(a) of AISI S100, with additional tests required when the deviation from the average demands them. The report records each configuration and its connection details, the load-versus-deformation curves, and the nature, type, and location of the failure exhibited by each specimen, supplemented by photographs — together with the standard’s required attestation that the assembly and testing were performed under the direction of an engineer in charge of testing. The measured quantities and the documented behavior are reported for use by a qualified engineer for its intended application.

Related assumptions

The assumptions on the line

  • Panel shear behavior

    The assembled panel provides the in-plane shear stiffness and strength the lateral system assigns to it.

    Fastener pattern, sidelap, and edge conditions move the number as much as the panel itself does — the details decide what the panel is worth.

  • Diaphragm connection load path

    The panel-to-frame and sidelap connections deliver the in-plane load path the diaphragm model assumes.

    Behavior is usually connection-governed — the connections reach their limit while the panel field still looks intact.

  • Assembled diaphragm stiffness

    The assembled diaphragm provides the in-plane stiffness the lateral analysis assigns to it.

    Connection slip and frame flexibility accumulate, so the built assembly is usually softer than a panel-only idealization predicts.

Related standards

Related standards

AISI S907 · test methodAISI S100 · referenced (test count, K2.1.1)AISI S310 · referenced design standardASTM E455 · alternative (simple span)

We test to the reference the standard defines — not to convenience.

Evidence visuals

What the setup and the numbers look like

Cantilever diaphragm shear diagram: steel panels fastened across a rectangular test frame, with sidelap marks along the panel joints and fastener marks along the support members, load P along one side and supports opposite, the sheared outline set against the dashed undeformed rectangle with the net deflection Δd and the frame dimensions a and b, plus an inset load–deflection curve marking Pmax and the 0.4 Pmax point.
An assembled panel is sheared in a cantilever frame — stiffness is read from the curve at forty percent of peak load.

Reading

Further reading

Certification relevance

Measured diaphragm behavior — Sn, G′, and F with documented failure modes — can form part of a certification evidence package for a custom or proprietary panel system. Testing and certification remain separate activities: the evidence supports engineering evaluation rather than creating a design value. SMHE does not grant approval from the authority having jurisdiction, permits, or product listings; those determinations stay with the AHJ or the applicable certification body.

Testing provides evidence; it does not itself certify a product. Certification is a separate function.

From testing evidence to certification

Questions engineers ask

Frequently asked questions

What is shear panel and diaphragm testing per AISI S907?

It is a laboratory test that loads a framed cold-formed steel panel assembly in its own plane using the cantilever test method and records how the assembly resists that in-plane shear. AISI S907 covers floor, roof, and wall diaphragm construction; a wall diaphragm — commonly called a vertical diaphragm or shear wall — is a wall designed to resist forces acting in the plane of the wall. What comes out is measured behavior: strength, stiffness, and the mechanism that governed.

What is actually tested — the panel, or the whole assembly?

The assembly. Steel panels are fastened to the test frame’s support members with structural fasteners and to each other along their edges with sidelap connections, both spaced as intended for end use, and the whole diaphragm is loaded as one system. That matters because a diaphragm’s response depends on the number, type, and size of its connections at least as much as on the panels themselves, so a panel coupon or an isolated fastener test answers a much narrower question.

What quantities does the test produce, and how are they used?

Three: the nominal diaphragm web shear strength per unit length, Sn; the diaphragm web shear stiffness G′, determined at forty percent of the maximum applied load; and the flexibility factor F = 1/G′. They are reported with the load–displacement record and the observed failure modes, and they describe the assembly that was tested. They reach a project through engineering evaluation, where a qualified engineer judges what they mean for the intended application — not by being carried across as design values.

Why is the bare frame tested before the panels go on?

Because the test frame itself carries part of the applied load, and that share does not belong to the diaphragm. AISI S907 has the bare frame — the support members assembled without panels — run through the same load test procedure, over a deflection range larger than the assembly will see, and its measured contribution is corrected out of both the strength and the stiffness results when it exceeds two percent of the corresponding load. Below that threshold the correction does not apply. Skipping the step would credit the panel system with resistance the frame supplied.

Does a test result prove code compliance or earn AISI S310 design values?

No. AISI S907 is a test method; it measures behavior. AISI S310 is the design standard, and design values with their safety and resistance factors are derived downstream under its own rules. A custom or proprietary wall panel does not earn S310 tabulated design values by being tested, and a test report is not a compliance determination. What the report provides is evidence — measured response, governing mechanism, and stated limits — for a qualified engineer to evaluate against the design basis.

When should a custom or proprietary wall panel system be tested, and how does that support an AMM submission?

When the system falls outside a clean prescriptive pathway and its in-plane behavior rests on an analytical model no one has checked against a built specimen. A defensible alternate methods and materials package can be assembled from a conservative analytical lower-bound basis, supporting test evidence, explicit limitations, and stated engineering judgment — without publishing a design value. The test supplies the evidence half: whether the assembly behaves the way the analysis assumed, and what actually governs when it does not.

Is this the assumption you need checked?

Tell us what you make, what changed, and what you need to know — we’ll confirm whether this test answers your question, or point you to the one that does.